Another late one... this time both units were failing on high pressure. Both units would hit 14psi in a matter of 10-15 min. All limits and controls check out. On a hunch I flipped the lead lag switch and now one unit is maintaining 8-10 psi consistently while the other is not being called. Looks like a worn selector switch.. and good luck on the money hunt to all my on call guys this week!!

Posted by cpolkowski at 2021-02-24 03:38:43 UTC