We ordered an new pan and pan heater to have on hand after taking this evap apart. We have had issues we water leakage and intermittent fuse pops. Found a compromised gasket and ice built around the electrical. We are going ahead with the new pan, as the other is warped slightly and new heater, as the cost is negligible in this high end facility. We also replaced the gasket and I will be adjusting the defrost to 6 times per day and 30 minutes from 4 times per day and 45 min. I have done this in the past with some good luck. Two birds with one stone #teachme Happy HVACing!