ok so don't mind me stuttering in the beginning it was still early and I didn't have my coffee so intermittent didn't come out properly lol ๐๐๐๐anyways customer had another company come twice and told them that they needed to change the gas valve and thermocouple ,so upon arrival she told me that's what the issue was and that's what needed to be changed.but me being me I had to troubleshoot and diagnose on my own and come with my conclusion. so I checked the gas valve it was opening and closing perfectly fine low voltage was good pilot flame steady blue flame ok long story short these honeywell s8610u ignition control have to be properly grounded to the pilot burner bracket because it send back a signal rectifying a flame to open up main valve on the ignition control problem solved and I didn't just go changing parts sometime the obvious is right in front of you #teachme #hvaclife #happyhvacing