I am out of ideas and need help. I was working on this Carrier unit issue was no cool. Saw the breaker inside the unit was tripped. It was the one going to the indoor blower motor. I checked for continuity among all leads all read 3.5. No continuity to ground. I turned the unit on the contactor was chattering bad. Found out the Y1 circuit was messed with bad. I re wired cooling circuit and I replaced the breaker and contractor for the blower. Unit turned on just fine, sequence was the contactor for the blower, then the contactor for the outside fans then the contactor for my first compressor (first stage cooling). After 10 minutes of it running continuously and checking out with EMS. Breaker trips again. My contactor stays pulled in for my blower even though there’s no power going to it due to the breaker tipping. My outdoor fan contactor stays pulled in forever never de-energizing but my compressor does pull out. YThe indoor blower section is small but I really did check the wires for any rub outs I can’t find the issue. I checked amps and the blower only amps up to 11amps during running and upon start up its 40amps. So if anyone has come across this please guide me in the right direction.
Posted by Kat95020 at 2026-07-06 23:40:41 UTC