Would this work? A previously tech installed this unit for a friend of mines with the piping of a 50 ft run..the liquid line is supposed to be 1/4 but he cut a by using the existing piping of 3/8...the 1/4 run to the condenser and evap is about a foot each, and the rest was 3/8( the pipping was in the ceiling) on an r32 unit...the existing pipeing was from a 3 ton unit , the new unit is a 2 ton...you guys think there will be any restrictions on refrigeration flow? FYI the suction line was 5/8 ...that run was ok..