According to CSA B52-2023 art. 6.8.4, for an installation through floors, the refrigerant piping may be carried in an approved rigid and tight continuous fire-resisting pipe duct or shaft without openings into floors not served by the refrigeration system. The pipe duct or shaft shall be vented to the outside or to the space served by the system. Has anyone faced this issue for new A2L split systems in a tall building? Do you know where to find fire-resisting pipe duct for this option?
Posted by spacehvac at 2026-02-28 19:50:57 UTC