Lennox RTU for process cooling at a food grade facility. 10% outside air. Figure some rough math of 70 degree room temp, 0 degree outside air, 63 degree return with a 20 degree coil design temp puts you around 43 degree suction temp so figure 33 degree saturation temp gives you 10 degrees of super heat (rough estimates here). The freeze protection thermistors are on the distribution tubes after the metering device instead of post evap after load has been applied. During cold windy nights the head pressure control setup and location of thermistors creates a situation that it will lock out for frozen evaporator. I changed the factory settings on the pressure control from 355 to 400 and lowered the hard start time on the dans to 3.5 seconds to reduce pressure swings, plan was to life the thermistors post evap but the thermistor design doesn’t allow it so I left them off until we return to wire in matching thermistors I can fix to the post evap suction. Also, am I really working on a fixed orfice stage 2 on a unit that needs NFC and Bluetooth to set up the controls 🤦🤦🤦