Working on a Goodman AC split system 410A with a piston metering device SP is 123.5 SLT is 43.8 vapor saturation is 41.9 SH is 1.9 HP is 290 LLT is 83.6 liquid saturation is 93.4 my SC is 9.8. Filter is clean, evap coil is clean my temp split is 11 and my return static is .54 and supply is 1.9 why is my temp split so low. Filter and evap coil are clean. Outdoor condenser is clean. Noticed the evap coil is an A frame and the top of the A is facing the heat exchanger instead of away. Why would my temp split be so low

Posted by mmccain15 at 2025-08-14 17:32:04 UTC